FlowMeasurement
-
LevelMeasurement
-
Related Instruments
Guidance Download
QR code
* Please scan the QR code with your smartphone to access this website page.
FC-100series is a liquid flow control system which consists of "FCV-200 Flow sensor + Control valve" and "FCA-100 Controller". FC-100 series is suitable for water and low viscosity liquids.
And it maintains stable flow even supply and/or load varies.
Flow sensor and control valve are integrated. This saves piping space.
DIN 24 x 48 size Controller saves panel space.
Control valve (FCV series)
Model | FCV-202A-1/4 | FCV-202A-3/8 | FCV-205A-3/8 | FCV-210A-3/8 |
---|---|---|---|---|
Measuring medium | Cooling water or low viscosity liquids (2mPa·s or less) Anticorrosive liquid |
|||
Nominal diameter | 1/4 | 3/8 | ||
Flow range | 0.4 to 2 L/min | 0.5 to 5 L/min | 1 to 10 L/min | |
Fluid Temperature | 0 to 60°C | |||
Fluid Pressure | 0.5MPa max. | |||
Process Connection | Rc1/4 | Rc3/8 | ||
Accuracy | ±3%F.S. |
Controller (FCA-100)
Input | Flow sensor: Open collector pulse |
---|---|
External setup signal: DC4 to 20mA , DC1 to 5V , DC0 to 10V | |
Main indication | 5 digit, 7segment LED indication for flow rate or setup, etc. |
Status display | 3 points LED Alarm indication 2 points(Red) Control indication 1 point(Green) |
Output | Flow rate signal: DC4 to 20mA, DC1 to 5V, DC0 to 10V Accuracy: ±1% F.S. |
Alarm: Open collector 2 points Abnormal output of valve: Open collector 1 point |
|
Front panel | 4 buttons "MODE", "Horizontal movement", "Vertical movement", "ENT." |
Power supply | DC24V±10% |
Construction | Panel for operation: Weatherproof(Equivalent to IP54) |
FlowMeasurement
LevelMeasurement
Related Instruments
Guidance Download
* Please scan the QR code with your smartphone to access this website page.