contact us

FC-100

FC-100 PDF

*Specifications are subject to change without prior notice.

FC-100series is a liquid flow control system which consists of "FCV-200 Flow sensor + Control valve" and "FCA-100 Controller". FC-100 series is suitable for water and low viscosity liquids.
And it maintains stable flow even supply and/or load varies.

Features

  • · Cost effective flow control system

  • · Space saving;

    Flow sensor and control valve are integrated. This saves piping space.
    DIN 24 x 48 size Controller saves panel space.

  • · Full open/close type valve is adopted, and can be used as Shut-off valve which has been indispensable.

  • · Drain out of line fluid by air purging possible

  • · Lead-free solder has become reality.

  • · High reliability of electronics

  • · EMC Compatible standard: EN61326-1

System diagram (Typical)

figure1

Recommended Applications

Continuous and stable feeding of cooling water for;

  • · Semiconductor / FPD plants and machinery
  • · Chiller units for air-conditioning
  • · Others

Standard Specifications

Control valve (FCV series)

Model Description
FCV-202A-1/4 FCV-202A-3/8 FCV-205A-3/8 FCV-210A-3/8
Connection size 1/4 3/8
Measuring fluids Cooling water or low viscosity liquids (2mPa·s or less)
Anticorrosive liquid
Fluid temperature 0 to 60°C (Without freezing)
Resisting pressure 0.5MPa
(1.0MPa is also available. Consult factory separately)
Controllable differential
pressure
0.2 to 0.4MPa
Control flow rate range 0.4 to 2 L/min 0.5 to 5 L/min 1 to 10 L/min
Cv value 0.1 0.3 0.6
Full open and
close time
Approx. 5 sec.
Response time Approx. 5 sec.
Type of flowmeter Axial flow wheel type (TW-090 series)
Material
Body: 
SCS14
Valve: 
SCS14
Valve spindle: 
SUS316
Wheel: 
Ferrite + Nylon 12
Ball: 
ZrO2
Shaft: 
ZrO2+PBT
Whirlpool guide: 
PBT
O-ring: 
Fluororubber
Piping connection Rc1/4 Rc3/8
Output of flowmeter Open collector pulse DC24V 15mA
Accuracy ±3%F.S.
Power supply Valve part: DC24V 700mA
Flowmeter: DC24V 50mA
Construction Valve part: Equivalent to IP54 (Except air hole)
Flowmeter: Equivalent to IP65
Ambient temperature
and humidity
0 to 50°C / 85%RH (Without freezing)
Wiring connection Connection with a specification electric wire

Controller (FCA-100)

Input Flow sensor: Open collector pulse
External setup signal: DC4 to 20mA , DC1 to 5V , DC0 to 10V
Main indication 5 digit, 7segment LED indication for flow rate or setup, etc.
Status display 3 points LED Alarm indication 2 points(Red)
Control indication 1 point(Green)
Output Flow rate signal: DC4 to 20mA, DC1 to 5V, DC0 to 10V
Accuracy: ±1% F.S.
Alarm: Open collector 2 points
Abnormal output of valve: Open collector 1 point
Front panel 4 buttons
"MODE", "Horizontal movement", "Vertical movement", "ENT."
Power supply DC24V±10%
Construction Panel for operation: Weatherproof(Equivalent to IP54)